Schneider Electric R9R85291 100A. 300mA, 2-Pole RCCB for LoadCentre KQ Distribution Board
Product Details
- Product or component type: Residual current circuit breaker
- Poles description: 2P
- [In] rated current: 100A
- Network type: AC
- Earth-leakage sensitivity: 300 mA
- Earth-leakage protection time delay: Instantaneous
- Earth-leakage protection class: Type AC
- Rated breaking and making capacity: Im 500 A conforming to BS EN 61008-1
- Rated conditional short-circuit current: 6 kA
- Network frequency: 50/60 Hz
- [Ue] rated operational voltage: 230 V AC 50/60 Hz
- [Ui] rated insulation voltage: 440 V
- [Uimp] rated impulse withstand voltage: 4 kV
- Control type: Toggle
- Local signalling: ON/OFF indication
- Mounting mode: Plug-in
- Mounting support: Socket
- 9 mm pitches: 4
- Dimensions (HxWxD): 96 x 36 x 78mm
-
Connections - terminals
- Tunnel type terminals (bottom) 1…35 mm ² rigid
- Tunnel type terminals (bottom) 1…25 mm ² flexible
- Standards: BS EN 61008
- Mechanical durability: 5000 cycles
- Electrical durability: 2000 cycles conforming to BS EN 61008-1
- Wire stripping length: 14 mm for bottom connection
- Tightening torque: 3.5 N.m bottom
- IP degree of protection: IP20
Specification
Depth |
78mm |
Gtin |
3606480652233 |
Height |
96mm |
Internal external |
Internal |
Mcbrcboincomerrccb amps |
100A |
No of mcbrcborcd poles |
2 Poles |
Product type |
RCD Units |
Weight |
0.55 |
Width |
36mm |