- Number of poles: 3P
- [In] rated current: 250A at 40 °C
- [Ue] rated operational voltage: 690 V AC 50/60 Hz conforming to EN/IEC 60947-2
- Suitability for isolation: Yes conforming to EN/IEC 60947-2
- Utilisation category: Category A
-
[Icu] rated ultimate short-circuit
breaking capacity: 36 kA Icu at 415 V AC 50/60 Hz conforming to EN 60947-2
- Performance level: F
- Trip unit name: Micrologic 2.2
- Trip unit technology: Electronic
- Trip unit protection functions: LSol
- Control type: Toggle
- [Ui] rated insulation voltage: 800 V AC 50/60 Hz conforming to EN/IEC 60947-2
-
[Uimp] rated impulse withstand
voltage: 8 kV conforming to EN/IEC 60947-2
-
[Ics] rated service short-circuit
breaking capacity: 36 kA at 415 V AC 50/60 Hz conforming to EN/IEC 60947-2
- Mechanical durability: 20000 cycles
-
Electrical durability:
- 20000 cycles at 440 V In/2
- 10000 cycles at 440 V In
- 10000 cycles at 690 V In/2
- 5000 cycles at 690 V In
-
Protection type:
- L : for overload protection (long time)
- So: for short time short-circuit protection with fixed delay
- I : for short-circuit protection (magnetic)
- Long-time pick-up adjustment type Ir (thermal protection): Adjustable
- [Ir] long-time protection pick-up adjustment range: 100...250 A
- Long-time protection delay adjustment type tr: Fixed
-
[Tr] long-time protection delay adjustment range:
- 400 s at 1.5 x Ir
- 16 s at 6 x Ir
- 11s at 7.2 x Ir
- thermal memory: 20 minutes before and after tripping
- Short-time protection pick-up adjustment type Isd: Adjustable
- [Isd] Short-time protection pick-up adjustment range: 1.5...10 x Ir
- Short-time protection delay adjustment type tsd: Fixed
- Instantaneous protection pickup adjustment type Ii: Fixed
- [Ii] instantaneous protection pick-up adjustment range: 3000 A
-
local signalling:
- Flashing LED (green) for ready to operate
- LED 105 % Ir (red) for overload
- LED 90 % Ir (orange) for overload
- Flashing LED (green) for ready to operate
- Dimensions (HxWxD): 161 x105 x 86mm
- Net weight 2.05 kg
-
Standards:
- EN/IEC 60947-1
- EN/IEC 60947-2
- Pollution degree 3 conforming to IEC 60664-1
- IP degree of protection: IP40 conforming to IEC 60529
Specification
Depth |
86mm |
Gtin |
5018934947020 |
Height |
161mm |
Internal external |
Internal |
Mcbrcboincomerrccb amps |
250A |
No of mcbrcborcd poles |
3 Poles |
Product type |
Outgoing Options |
Width |
105mm |