Fike 540-0001 CIE-A-400 Addressable Fire Alarm Control panel
PRODUCT DESCRIPTION
The CIE-A-400 Addressable Fire Alarm Control Panel features up to two loops, each capable of supporting up to 200 devices*, with a maximum loop length of 2KM. The panel includes two configurable Monitored Input Circuits, two configurable Monitored Output Circuits, two configurable Relays, one Fault Relay, and a Peripheral Bus Circuit that can connect up to 8 Repeater Panels.
Fike 540-0003 Loop Driver Card required to function as 2-Loop panel.
The system allows configuration across three alarm stages with full ‘Zone to Zone’ Cause and Effect functionality across all 32 panel zones, and includes options for Alarm Confirmation and Delay Timers. Additionally, there are 32 output zones available for more advanced Cause and Effect programming.
The CIE-A-400 is fully compatible with Fike’s addressable range of devices and employs soft addressing, removing the need for installers to manually address each device and preventing issues caused by duplicate addresses. The devices’ operating parameters are configured via the panel or OSP programming software and stored directly in the device’s flash memory. This advanced digital protocol reduces the amount of data exchanged between the detector and control panel, ensuring faster and more reliable communication
TECHNICAL DETAILS
- Dimensions Panel (WxHxD): 353mm x 333mm x 117mm
- Operating Temperature: -5°C to +40°C
- IP Rating IP30
- Mains Supply Input: 230V AC Nominal
- Standby Battery Requirement: 2 x 7/9Ah 12V Sealed Lead Acid (2 x 12/17Ah with extended battery box)
- Max Number of Loops: 2
- Max Loop Length: 2000 Metres
- Max Conductor Resistance: 24 Ohms
- Loop Loading: 450 DLU (200 Devices Max)*
- Loop Operating Voltage: 40V DC
- Standby: 24V DC
- Max Loop Current: 500mA
- Number of Supported Zones: 32
- LCD Display: LCD Graphical Display
- Device Labels: 31 Characters
- Event Log: 1000 Events
- Repeater Panels: 8 Max
- Aux Power Output: 30V DC 350mA
- Inputs and Outputs:
- Inputs: 2 x Monitored Inputs (3k3 EOL, 680R Firing Resistor)
- Outputs: 3 x Volt Free Relay (30V DC @ 1A Max)
- Monitored Outputs 2 x (32V DC @ 250mA Max, 10k EOL).
- Each monitored output may be configured as a Conventional Sounder Circuit,
- Fire Output or as a Common Fault Output.
*Please check the CIE-A-400 device loading unit (DLU) calculation sheets for accurate loop loading calculations.:
Specification
Product type |
Fire Alarm |
Size |
Iiyama |
Downloads
Download product data sheets