ESP MAG2P 2 Zone Panel Polycarbonate Casing
Product Details
- 2 programmable zones
- Active end of line monitoring and head removal
- 30 fire detectors per zone
- Unlimited number of call points per zone
- Integral sound alarm button
- 'Class change' facility
- Enable/disable security key
- One man walk test facility
- Volt free fire change over relay
- Volt free fault change over relay
- Individual sounder circuit fault ID
- Individual zone/sounder isolate
- CE certified to EN54 P2/4
- Requires only 1x12v battery
- MAG2P - ABS casing
Product Details
- Max Detectors Per Zone: 30
-
Thresholds for Zone Conditions:
- 0 - 2 mA (Fault condition)
- 2 - 6 mA (Normal condition)
- 6 - 110 mA (Fire condition)
- 110 mA - Short (Fault condition)
- Mains Fail Consumption: 50mA
- Mains Supply: 230 VAC
- Standby Supply: 1 x 7ah 12V S.L.A. Battery
- Power Availability: 0.7 amps
- Sounder 1: 24V (max 300mA fused)
- Sounder 2: 24V (max 300mA fused)
- Fault/Fire Relay: Volt free 500mA @ 24V (max load)
- Auxiliary Output: 24VDC (300mA fused)
- Working Temperature: 0 to 40 ºC
- Storage Temperature: -20 to 60 ºC
- Humidity: 0 - 95%
- Dimensions: 340 x 290 x 100mm
- Weight: 2.1Kg
Specification
Product type |
Fire Alarm |
Size |
Iiyama |